Powder based fire extinguisher, portable, 1000 kg, model P100
TECHNICAL SPECIFICATIONS
|
Extinguishing agent |
Dry chemical powder ABC 40 HJ ABC Universal |
|
Propellant gas |
Nitrogen (N2) |
|
Nominal quantity of powder |
100 kg |
|
Capacity of the cylinder |
114 l +/-0,05% |
|
Working pressure min/max |
14 – 18 bars |
|
Testing pressure |
27 bars |
|
Assembly drawing |
Drawing no.: TN / EN-100P-03 |
|
Body of the extinguisher |
Drawing no.: ZX-1C-07-00 |
|
Valve |
Drawing no.: HD-BP-03, HD-BP-02 |
|
Hose assembly |
Drawing no.: 23A002 |
|
Manometer |
Drawing no.: HZ-BP-01 |
|
Body material |
Shaped steel |
|
Body diameter |
400 mm |
|
Height of the extinguisher |
1230 mm |
|
Welds |
Two horizontal and one vertical |
|
Manufacturer / CE no. |
TN / CE0029 |
|
No. of EN 3-7 certificate |
EX-C-403/EN1866/B/01/15 |
|
Issuing Notified Body |
MIRTEC SA – Volos, CE0437 |
SPECIFICATIONS OF USE
|
Model |
Permanently pressurized |
|
Fire rating |
A III B |
|
Temperature range |
-30°C to +60°C |
ADITIONAL USE
|
Suitable for use on live electrical equipment as well, up to 1000 V, from 1m distance. |
MARKING
|
The marking of the extinguisher must contain information according to SR EN 1866-1:2008. Each extinguisher must be provided with a label that must be placed on the extinguisher’s body. It is made up of 5 parts, as follows: First part includes:
STINGATOR P100
100 kg powder ABC 40
A III B Second part includes:
Third part includes:
Fourth part includes:
Fifth part include:
|
IMPORTANT
|
Under no circumstances should the label be removed or destroyed. Otherwise, the extinguisher can’t be identified or serviced at its due date. |
STORAGE
|
Powder based fire extinguisher, portable, 100 kg, model P00, must be stored in clean and dry spaces at temperatures between - 30 ° and + 60 ° C. |