Foam based fire extinguisher, portable, 100 l, model SM100
TECHNICAL SPECIFICATIONS
|
Extinguishing agent |
Foam “Fomtec AFFF 6%” |
|
Propellant gas |
Nitrogen (N2) |
|
Nominal quantity of foam |
100 liters |
|
Cylinder capacity |
114 l |
|
Working pressure min/max |
14-18 bars |
|
Testing pressure |
27 bars |
|
Assembly drawing |
Drawing no.: GEF/EN-100S-00 |
|
Extinguisher body |
Drawing no.: TN / EN-100F-03 |
|
Valve |
Drawing no.: ZX-1C-07-00 |
|
Hose assembly |
Drawing no.: HD-PB-03, HD-PB-01 |
|
Manometer |
Drawing no.: HZ-BP-02 |
|
Body material |
Drawing no..: LH-3323; 23A038 |
|
Body diameter |
Shaped steel |
|
Height of the extinguisher |
400 mm |
|
Weight of extinguisher (with foam) |
1210 mm |
|
Manufacturer/ CE cylinder No. |
Two horizontal and one vertical |
|
No. of EN 3-7 certificate |
TN / CE0029 |
|
Issuing Notified Body |
EX-C-405/EN1866/B/01/15 |
|
|
MIRTEC SA – Volos, CE0437 |
SPECIFICATIONS OF USE
|
Model |
Permanently pressurized |
|
Fire rating |
A III B |
|
Temperature range |
From +5° C to +60° C ATTENTION : RISK OF FREEZING! |
USE
|
For extinguishing fire classes A and B. Do not use on live electrical equipment!!! |
MARKING
|
The marking of the extinguisher must contain information according to SR EN 1866-1:2008. Each extinguisher must be provided with a label that must be placed on the extinguisher’s body. It is made up of 5 parts, as follows: First part includes:
STINGATOR SM100
100 l Fomtec AFFF6% foam
A III B Second part includes:
Third part includes:
Fourth part includes:
Fifth part include:
|
IMPORTANT
|
Under no circumstances should the label be removed or destroyed. Otherwise, the extinguisher can’t be identified or serviced at its due date. |
STORAGE
|
Foam based fire extinguisher, portable, 100 l, model SM100 must be stored in clean and dry spaces at temperatures between 0 ° and + 60 ° C. |
Purchase from: https://www.magazin-stingatoare.ro/stingator-sm100_p_15.html